FRICTION LOSS DATA
Pressure loss & equivalent length of Daejin flexible sprinkler hose drop
Summary of pressure loss & equivalent length for 700 mm flexible hose with two 90° bend and
T terminated in a ½” outlet reducer – Daejin Flexible hose sprinkler Drop
Flow rate (l/min) | Pressure upstream(bar) | Pressure downstream(bar) | Corrected pressure loss (bar) | Eqivalent Length |
40 | 0.31 | 0.20 | 0.005 | 0.40 |
60 | 0.75 | 0.49 | 0.077 | 3.00 |
80 | 1.43 | 0.93 | 0.199 | 4.56 |
100 | 2.22 | 1.44 | 0.321 | 4.89 |
120 | 3.22 | 2.08 | 0.483 | 5.23 |
150 | 5.01 | 3.23 | 0.751 | 5.38 |
Average equivalent length – 3.90