New sprinkler connection piping Flexible Sprinkler Drops

The Genie System new sprinkler piping is designed to significantly reduce wages and assembly costs.
By essentially blocking pipe cutting and mid-pipe connections, you can save time and money efficiently.

The Genie System new sprinkler connection piping is 700/1000/1200/1500 / 1800mm hose length Braid and Unbraid type which can be assembled with various kinds of brackets on the top and front part of ceiling and wall structure. Especially, it can be installed on structure T-BAR, metal ornaments, Hat channel, wood beams, concrete sidewalls and so on. The Genie System is certified for use in commercial hotels, restaurants, cultural centers, entertainment, educational institutions, public institutions, athletic facilities, and religious buildings.

   

DJ25UB

  • 1. Tubular flexible tube
  • 2. Reduce
  • 3. Nipple
  • 4. Slip nut
  • 5. Pressing ring
  • 6. Gasket

SPECIFICATIONS

Manufacturable length 700mm, 1000mm,1200mm,
1500mm, 1800mm
outlet 1/2” or 3/4”
Hose type Unbraided
hose Stainless Steel 304
Nuts & Nipples Metal zinc plating
Sealing Gasket
/ Isolation Ring
EPDM / NYLON
Maximum attention temperature 225℉
Maximum working pressure 175 psig (UL/ULC)
New sprinkler hose related reducer / nipple assembly Permissible torque: 300 kgf.cm
Minimum bending radius 100 mm from the connecting nut (UL / ULC)
Connector Metal zinc plating
Inlet 1”NPT or BSP
Outlet 1/2” or 3/4”NPT or BSP

Model Rated Pressure, psig Max. Ambient Temp, °F Nom. Inlet by Outlet Size, in. Assembly Length, ft (mm) Max No. of 90° Bends Min Bend Radius, mm. Equivalent Length of 1 in. Schedule 40

Steel Pipe (C = 120), ft

Flexibility Type
DJ25UB-700 175 225 1×1/2 700 1 100 24 Limited
DJ25UB-1000 175 225 1×1/2 1000 2 100 44 Limited
DJ25UB-1200 175 225 1×1/2 1200 2 100 49 Limited
DJ25UB-1500 175 225 1×1/2 1500 2 100 59 Limited
DJ25UB-1800 175 225 1×1/2 1800 3 100 84 Limited

 

DJ25UB-

700

175 225 1×3/4 700 1 100 30 Limited
DJ25UB-1000 175 225 1×3/4 1000 2 100 48 Limited
DJ25UB-1200 175 225 1×3/4 1200 2 100 55 Limited
DJ25UB-1500 175 225 1×3/4 1500 2 100 64 Limited
DJ25UB-1800 175 225 1×3/4 1800 3 100 86 Limited

Table 1 : Summary of pressure loss & equivalent length for 700 mm flexible hose with one 90° bend and
terminated in a ½” outlet reducer – Daejin Flexible sprinkler Drop – DJ25UB

Flow rate
(l/min)
Pressure
upstream(bar)
Pressure
downstream(bar)
Corrected pressure loss
(bar)
Eqivalent Length
40 0.31 0.20 0.005 0.40
60 0.75 0.49 0.077 3.00
80 1.43 0.93 0.199 4.56
100 2.22 1.44 0.321 4.89
120 3.22 2.08 0.483 5.23
150 5.01 3.23 0.751 5.38

Average equivalent length – 3.90

Table 2Summary of pressure loss & equivalent length for1000 mm flexible hose with one 90° bend and
terminated in a ½” outlet reducer – Daejin Flexible sprinkler Drop – DJ25UB
Flow rate
(l/min)
Pressure
upstream(bar)
Pressure
downstream(bar)
Corrected pressure loss
(bar)
Eqivalent Length
40 0.34 0.20 0.035 2.88
60 0.93 0.52 0.227 8.86
80 1.66 0.92 0.439 10.06
100 2.62 1.43 0.731 11.09
120 3.79 2.05 1.083 11.73
150 6.05 3.24 1.781 12.76

Average equivalent length – 9.56

Table 3 :
Summary of pressure loss & equivalent length for 1200 mm flexible hose with one 90° bend and terminated in a ½” outlet reducer – Daejin Flexible sprinkler Drop – DJ25UB
Flow rate
(l/min)
Pressure
upstream(bar)
Pressure
downstream(bar)
Corrected pressure loss
(bar)
Eqivalent Length
40 0.36 0.20 0.055 4.53
60 0.97 0.52 0.267 10.42
80 1.73 0.92 0.509 11.67
100 2.75 1.43 0.861 13.06
120 4.02 2.07 1.293 14.00
150 6.32 3.21 2.081 14.91

Average equivalent length – 11.43

Table 4 :
Summary of pressure loss & equivalent length for 1500 mm flexible hose with one 90° bend and terminated in a ½” outlet reducer- Daejin Flexible sprinkler Drop – DJ25UB   
Flow rate
(l/min)
Pressure
upstream(bar)
Pressure
downstream(bar)
Corrected pressure loss
(bar)
Eqivalent Length
40 0.37 0.20 0.065 5.36
60 0.98 0.52 0.277 10.81
80 1.76 0.93 0.529 12.13
100 2.77 1.43 0.881 13.37
120 4.03 2.08 1.313 14.22
150 6.35 3.22 2.101 15.06

Average equivalent length – 11.82

Table 5Summary of pressure loss & equivalent length for 1800 mm flexible hose with one 90° bend and terminated in a ½” outlet reducer – Daejin Flexible sprinkler Drop – DJ25UB

Flow rate
(l/min)
Pressure
upstream(bar)
Pressure
downstream(bar)
Corrected pressure loss
(bar)
Eqivalent Length
40 0.40 0.19 0.105 8.66
60 1.05 0.51 0.357 13.93
80 1.93 0.92 0.709 16.25
100 3.05 1.44 1.151 17.46
120 4.38 2.05 1.673 18.12
150 7.04 3.25 2.761 19.79

Average equivalent length – 15.70

UNBRAIDED FLEXIBLE HOSE UL/LPCB

Part # Description Part # Description
DJ25UB-700 1/2”x700mm Unbraided hose DJ25UB-700 3/4”x700mm Unbraided hose
DJ25UB-1000 1/2”x1000mm Unbraided hose DJ25UB-1000 3/4”x1000mm Unbraided hose
DJ25UB-1200 1/2”x1200mm Unbraided hose DJ25UB-1200 3/4”x1200mm Unbraided hose
DJ25UB-1500 1/2”x1500mm Unbraided hose DJ25UB-1500 3/4”x1500mm Unbraided hose
DJ25UB-1800 1/2”x1800mm Unbraided hose DJ25UB-1800 3/4”x1800mm Unbraided hose

* OD : 25.1mm / ID : 21.4mm STS 304

Genie System Extension Spooler Piping Overseas Certification Standard
  • Underwriter’s Laboratories, Inc. (UL/ULC), cUL us 2443Specification of new sprinkler piping and its accessories for fire safety service
  • 2Loss Prevention Certification Board (LPCB)Sprinkler system expansion and contraction test specification
  • 3National Fire Protection Association (NFPA)

    NFPA 13Specification of new sprinkler piping and its accessories for firefighting service

    NFPA 13DHan / Two Family Residential Facilities and Manufacturing Plant Sprinkler System Installation Specification

    NFPA 13R4 or above residential building sprinkler system installation standard

    NFPA 13
    Section 9.2.1.3.3.3Not more than 6 feet long without hangers Installation of flexible connection piping

  • 4American Society for Testing and Methods (ASTM)

    ASTM C635sound absorption tile rail panel ceiling metal suspension System-Related Manufacturing, Testing, and Specification

    ASTM C636Hinged Tile Rail Panel for Metal Suspension System Specification for installation of ceiling structure

  • 5International Building Code (IBC) Section 1621 /
    American Society of Civil Engineers (ASCE)
    7.9.6.2.6.2 & 9.6.2.6.2.2
    Alternative solutions that can be installed without earthquake evacuation New sprinkler connection piping